Key features
High-level product advantages presented in a cleaner review format.
2000W/VA Pure Sinewave Output
Delivers stable power with automatic voltage regulation for sensitive equipment.
Advanced Touchscreen LCD
Customizable interface for user preferences and intuitive operation.
Performance Logging & User Alarms
Built-in loggers, user-defined alarms, and logic-based automation for proactive management.
Dual Ethernet & Secure Remote Access
SNMPv3, HTTPS, and two Ethernet ports for robust and secure connectivity.
USB Host Functionality
Fast firmware upgrades, configuration cloning, and reliable data backups.
Temperature-Compensated Charging
Maximizes battery life with intelligent charging and robust surge protection.
Comprehensive System Monitoring
CAN, dry contacts, and environmental sensors for full system awareness.
Hardened Environmental Design
Operates reliably in extreme temperatures from -40°C to 74°C.
Standards Compliant
Complies with UL 1778, CAN/CSA-C22.2 No. 107.3, FCC Part 15 Class A and ICES-003 Class A, and is RoHS compliant; EN 62040-1, EN 62040-2 and the CE mark apply to the 230 VAC version only.
Specifications
Dedicated technical preview for quick review.
- Dimensions
- 133H x 394W x 222D mm (5.22H x 15.5W x 8.75D in)
- Weight
- 18 kg (40 lb)
- Operating Temperature
- -40°C to 74°C (-40°F to 165°F). The 120 VAC module derates after 50°C (122°F) and the 230 VAC module after 55°C (131°F), by 1.4% per °C up to a maximum of 74°C
- Humidity
- Up to 95% (non-condensing)
- Altitude
- Up to 3700 m (12,000 ft); derates 2°C per 300 m (1000 ft) above 1400 m (4500 ft)
- Audible Noise
- 45 dBa at 1 metre (39 in), measured at 25°C ambient temperature
- MTBF
- 250K+ hours per Telcordia SR-332 (100% duty cycle, full load, 40°C)
- BTU/hr, Normal Mode
- 120 VAC model: 57 W / 194.5 BTU/hr; 230 VAC model: 48 W / 163.8 BTU/hr
- BTU/hr, Backup Mode
- 120 VAC model: 361.94 W / 1235 BTU/hr; 230 VAC model: 347.3 W / 1185 BTU/hr
- 120 VAC Model, Battery
- 48 VDC string voltage; 80 A battery breaker; 15 A maximum charging current
- 120 VAC Model, Input
- 120 VAC nominal; 85 to 150 VAC range; 50 Hz or 60 Hz ±5% (frequency autodetect by default, can also be configured manually); 20 A at nominal voltage and maximum battery charging current; 25 A AC breaker
- 120 VAC Model, Output
- Pure sinewave; 120 VAC nominal; voltage regulation ±10% in line mode, ±2% in inverter mode; 2000 W/VA at 50°C; output frequency equals input frequency; frequency tolerance in backup mode ±0.3 Hz
- 230 VAC Model, Battery
- 48 VDC string voltage; 80 A battery breaker; 15 A maximum charging current
- 230 VAC Model, Input
- 210/220/230/240 VAC nominal; 153 to 322 VAC range; 50 Hz or 60 Hz ±5% (frequency autodetect by default, can also be configured manually); 12 A at nominal voltage and maximum battery charging current; 15 A input breaker
- 230 VAC Model, Output
- Pure sinewave; 210/220/230/240 VAC nominal (same as input); voltage regulation ±10% in line mode, ±2% in inverter mode; 2000 W/VA at 55°C; output frequency equals input frequency; frequency tolerance in backup mode ±0.3 Hz
- Typical Output Voltage THD (resistive load)
- 120 VAC model: less than 3%; 230 VAC model: less than 5%
- Typical Efficiency (resistive load)
- 120 VAC model: 97.5%; 230 VAC model: 97% (at nominal AC input, full load and 25°C ambient temperature)
- Typical Transfer Time
- Less than 5 ms
- Load Crest Factor
- 3:1 (load dependent)
- Lightning/Surge Protection
- ANSI/IEEE C62.41.2:2002, Criteria A & B
- SNMP
- SNMP v3 via Ethernet; compatible with subscription and discovery services
- TCP/IP
- IPv4 or IPv6
- SMTP via Ethernet
- Security
- 256-bit password encryption; SSL for the HTTPS secured web interface
- Display
- Full graphic LCD, 480 x 272 pixels, resistive touch screen
- Ports
- 2 x RJ45 Ethernet; 1 x RJ11 for battery temperature compensation; 1 x RJ12 for Alpha CAN devices; 1 x USB-A for upgrades or file management with a standard USB flash drive; 1 x USB-Mini B for soft shutdown using the MegaTec protocol
- Indicators
- Solid green: line mode; flashing green: inverter mode; yellow/amber: minor alarms; red: major/critical alarms
- Dry Contacts
- Programmable NO/NC (250 VAC, 1 A), 3 user inputs, ATS
- Factory Defaults
- C1: On Battery; C2 and C3: Low Battery + No Line; C4: Load Shed Timer 1; C5: Alarm; C6: 48 VDC at 500 mA (factory configurable only); C7: user inputs (S1: self test, S2: user input, S3: shutdown/EPO); C8: ATS (48 VDC at 10 mA)
- Power Connectors, 120 VAC Model
- Standard (0170022-001): terminal block input and output; optional (0170022-002): terminal block input, terminal block plus dual 5-15R output
- Power Connectors, 230 VAC Model
- Standard (0170022-101): terminal block input and output
- Electrical Safety
- UL 1778, CAN/CSA-C22.2 No. 107.3; EN 62040-1 (230 VAC version only)
- Marks
- cCSAus; CE (230 VAC version only)
- EMC
- CFR Title 47 FCC Part 15 Class A, ICES-003 Class A; EN 62040-2 UPS Category C2 (230 VAC version only)
- RoHS
- Yes